Shaded bands are the occupied periods; timed heating starts earlier by the lead time you set. Dashed blue is the outdoor temperature.
U-value tells you how fast a house leaks heat. How you control the heating decides how much gas you actually burn, what it costs, and whether the house is warm when you need it. Change the house or the controls and every result updates.
Shaded bands are the occupied periods; timed heating starts earlier by the lead time you set. Dashed blue is the outdoor temperature.
Cold = share of occupied time more than 1 °C below the setpoint. Warm = more than 2 °C above it. The heat pump columns deliver the same heat, using the COP and electricity price you set.
In the experiment, the jar of water cooled according to
The house is the same equation with a heater and internal gains added:
H is the heat loss coefficient (W/K): U × envelope area, plus 0.33 × air changes × volume for ventilation. C is the heat capacity of the building fabric. The ratio C/H is the time constant τ, the same quantity you fitted from the jar's cooling curve.
Always on holds the setpoint around the clock: most comfortable, highest heat loss, because the inside stays warm all night.
Timer only runs the radiators flat out during the periods with no room thermostat, so it overshoots on mild days and wastes gas.
Timer + thermostat stops the overshoot. The house cools between periods, which cuts losses, but a slow, leaky house may still be cold at the start of each period.
Setback keeps a lower floor overnight: a trade-off between cost and comfort.
Model: a single-zone resistor–capacitor (RC) model stepped every 2 minutes over a representative day each month. Radiator output scales with (flow − room temperature)1.3. Radiators are sized to meet the design load at −3 °C outside at the chosen flow temperature. Outdoor temperatures are approximate Cork monthly means with a ±3 °C daily swing. Solar gain and hot water are not included.